Input Voltage (specify one) | 115 V ±10%, 50/60 Hz, 30 A (at full rated output) |
230 V ±10%, 50/60 Hz, 20 A |
Output Current | To provide a variety of test circuit impedances, six output taps with two ranges are provided |
High Range | 2.00 to 10.00 A at 100 V max |
3.00 to 15.00 A at 66.6 V max |
8.00 to 40.00 A at 25 V max |
10.00 to 50.00 A at 20 V max |
20.00 to 100.0 A at 10 V max |
34.00 to 170.0 A at 5.9 V max |
Output Power | 1000 VA |
Low Range | 2.00 to 10.00 A at 50 V max |
3.00 to 1 5.00 A at 33.3 V max |
8.00 to 40.00 A at 12.5 V max |
10.00 to 50.00 A at 10 V max |
20.00 to 100.0 A at 5 V max |
34.00 to 170.0 A at 2.95 V max |
Output Power | 500 VA |
Accuracy | Typical: | ±0.5% of setting |
Maximum: | ±1.0% of setting |
Alarm will indicate when amplitude, phase angle, or waveform is in error |
Resolution | Four ranges: | 0.01 A |
Two ranges: | 0.l A |