Specifications are valid at nominal input voltage and an ambient temperature of +25°C, (77°F).
Environmental |
Application field | The instrument is intended for use in medium and high-voltage substations and industrial environments. |
Ambient temperature |
Operating | -20°C to +50°C (-4°F to +122°F) |
Storage | -20°C to 70°C (-4°F to +158°F) |
Humidity | <90%RH, non-condensing |
Mains voltage | 90 – 264 V AC, 47 – 63 Hz |
Dimensions | 305 x 194 x 360 mm (12" x 7.6" x 14.2") |
Weight | 6 kg (13 lbs) |
Measurement |
FRA Method | Sweep frequency (SFRA) |
Frequency range | 0.1 Hz – 25 MHz, user selectable |
Number of points | Default 1046, User selectable up to 32,000 |
Measurement time: | Default 64 s, fast setting, 37 s (20 Hz – 2 MHz) |
Points spacing | Log., linear or both |
Dynamic range/Noise floor | >130dB |
Inaccuracy | ±0.5 dB down to -100 dB (10 Hz – 10 MHz) |
IF bandwidth/Integration time | User selectable (10% default) |
Software | FRAX for Windows 2000/ XP/Vista/7 |
Standards / guides | Fulfill requirements in Cigré Brochure 342, 2008 Mechanical condition assessment of transformer windings using FRA and Chinese standard DL/T 911-2004, FRA on winding deformation of power transformers, as well as other international standards and recommendations |
Analog Output |
Channels | 1 |
Compliance voltage | 0.2 – 24 V p-p |
Measurement voltage at 50 Ω | 0.1 – 12 V p-p |
Output impedance | 50 Ω |
Protection | Short-circuit protected |
Analog Input |
Channels | 2 |
Sampling | Simultaneously |
Input impedance | 50 Ω |
Sampling rate | 100 MS/s |
PC |
Operating system | Windows® based |
Memory | 1000 records in internal memory External storage on USB stick |