Fluke 80i-600 AC Current Probe
The Model 80i-600 is a clamp-on ac current probe designed to extend the current measuring capability of an ac current meter to 600 amperes. A clamp-on, 1000-turn coil designed into the probe allows measurements to be made without breaking the circuit under test. The coil serves as the secondary of a current transformer. The current carrying conductor being measured serves as the primary. Because of a high efficiency, quadrature type of winding used. wire size and the position of the wire within the probe jaws does not effect accuracy.
Output: | I milliamp per ampere of input current (1 mAlA) |
Accuracy: | Accuracy: ±2% of reading, 50 Hz to I kHz. ±3% of reading (typical). 30 Hz to 50 Hz or I kHz to 10 kHz. |
Working Voltage: | 750V ac rms maximum |
Maximum Conductor Size: | 50.8 mm (2 inch.) |
Shunt (load) Resistance: | less than 12 ohms at multimeter input to maintain specified accuracy |
Typical Bandwidth: | ~10% at 10 Hz and 50 kHz (lA, 400 Hz reference, excludes multimeter response) |
Usable Current Range: | 0.IA. to 2000A, 5 seconds maximum above 600A |
Safety: | Protection Class Class II as defined in IEC 348 and ANSI C39.5 |
- Current Range: 1A to 600A AC (2000A Peak)
- Basic Accuracy: +/- 2% of reading
- Output Signal: 1mA / A
- Frequency Range: 30Hz to 10kHz
- Working Voltage: 750V AC rms
- Maximum Conductor Size: 50.8mm (2.0 inch) diameter
- Safety Rating: Protection Class II as defined in IEC 348 and ANSI C39.5