Temp Only |
EGNZ12-4CWL EGNZ12-4CAL |
EGNZ12-6CWL EGNZ12-6CAL |
EGNZ12-7.5CWL |
Temperature Range |
-70 to 180°C (-94 to 354°F) |
Cooling Capacity |
2.5 kW at -50°C |
3.6 kW at -50°C |
4 kW at -50°C |
Refrigeration System |
Cascade 4 hp Scroll |
Cascade 6 hp Scroll |
Cascade 7.5 hp Scroll |
Heating System |
5 kW |
8 kW |
8 kW |
Humidity Range |
10 to 95% RH per chart (EGNX models only) |
Measured Airflow |
850 cubic meters per hour (500 CFM) |
Performance Example (-40°C to 85°C with 50 lbs. Aluminum) |
Heating Rate |
7°C/m average |
15.5°C/m average |
15.5°C/m average |
Cooling Rate |
5.5°C/m average |
11°C/m average |
15.5°C/m average |
Dimensions |
Workspace Volume |
380 L (12 cu. ft.) |
Workspace (WxDxH) |
600 x 743 x 850 mm (23.6" x 29.25" x 33.5") |
Exterior (WxDxH) |
889 x 2103 x 1768 mm (35" x 83" x 70") (‘CAL’ suffix models are 36 cm (14") taller) |
Site Requirements |
Power Supply |
460V 3Ø 60Hz (380-415V 3Ø 50Hz also available) |
Humidity Water |
De-ionized water, 0.2 to 10 µS/cm resistivity (EGNX models only) |
Cooling Water Maximum with 30°C Inlet |
34 LPM (9 GPM) (CWL suffix models) |
53 LPM (14 GPM) (CWL suffix models) |
72 LPM (19 GPM) |
Heat to Room |
40,000 BTU/hr (CAL suffix models) |
60,000 BTU/hr (CAL suffix models) |
— |